Provides for both visual monitoring and electronic control of very low differential pressure. Ideal for control applications in building HVAC/R systems where local indication is desired during routine maintenance checks or necessary when trouble shooting the system.
Provides for both visual monitoring and electronic control of very low differential pressure. Ideal for control applications in building HVAC/R systems where local indication is desired during routine maintenance checks or necessary when trouble shooting the system.
Gauge Specifications:
Service: Air and non-combustible, compatible gases.
Accuracy: +/-2%.
Stability: ±1% F.S./yr.
Pressure Limits: 2 psi (13.79 kPa).
Temperature Limits: 20 to 120°F (-6.67 to 48.9°C).
Process Connections: 1/8" female NPT.
Size: 4" (101.6 mm) dial face, 5" (127 mm) O.D. x 2-11/16" (68.3 mm).
Weight: 1 lb, 12.6 oz (811 g).
Agency Approvals: CE.
Transmitter Specifications:
Accuracy: +/-0.5% (includes linearity, hysteresis, repeatability).
Temperature Limits: 20 to 120°F(-6.67 to 48.9°C).
Compensated Temperature Range: 32 to 120°F (0 to 48.9°C).
Thermal Effect: ±0.025% F.S./°F (0.045% F.S./°C).
Power Requirements: 10-35 VDC (2-wire).
Output Signal: 4 to 20 mA.
Zero and Span Adjustments: Protected potentiometers.
Loop Resistance: DC; 0-1250 ohms maximum.
Current Consumption: DC; 38 mA maximum.
Electrical Connections: Screw terminal block.
Mounting Orientation: Diaphragm in vertical position.
Gauge | |
Service | Air and non-combustible, compatible gases |
Stability | ±1% FS/yr |
Temperature Limits | 20 to 120°F (-6.67 to 48.9°C) |
Process Connections | ⅛" female NPT |
Size | 4" (101.6 mm) dial face, 5" (127 mm) OD x 2-11/16" (68.3 mm) |
Weight | 1 lb, 12.6 oz (811 g) |
Agency Approvals | CE |
Transmitter | |
Temperature Limits | 20 to 120°F (-6.67 to 48.9°C) |
Compensated Temperature Range | 32 to 120°F (0 to 48.9°C) |
Thermal Effect | ±0.025% FS/°F (0.045% FS/°C) |
Power Requirements | 10 to 35 VDC (2-wire) |
Output Signal | 4 to 20 mA |
Zero and Span Adjustments | Protected potentiometers |
Loop Resistance | DC: 0 to 1250 Ω maximum |
Current Consumption | DC: 38 mA maximum |
Electrical Connections | Screw terminal block |
Mounting Orientation | Diaphragm in vertical position |
Click on a category to view a selection of compatible accessories with the Dwyer 605-10 Magnehelic Differential Indicating Transmitter (0-10\w.c.)".
Gauge | |
Service | Air and non-combustible, compatible gases |
Stability | ±1% FS/yr |
Temperature Limits | 20 to 120°F (-6.67 to 48.9°C) |
Process Connections | ⅛" female NPT |
Size | 4" (101.6 mm) dial face, 5" (127 mm) OD x 2-11/16" (68.3 mm) |
Weight | 1 lb, 12.6 oz (811 g) |
Agency Approvals | CE |
Transmitter | |
Temperature Limits | 20 to 120°F (-6.67 to 48.9°C) |
Compensated Temperature Range | 32 to 120°F (0 to 48.9°C) |
Thermal Effect | ±0.025% FS/°F (0.045% FS/°C) |
Power Requirements | 10 to 35 VDC (2-wire) |
Output Signal | 4 to 20 mA |
Zero and Span Adjustments | Protected potentiometers |
Loop Resistance | DC: 0 to 1250 Ω maximum |
Current Consumption | DC: 38 mA maximum |
Electrical Connections | Screw terminal block |
Mounting Orientation | Diaphragm in vertical position |